Benchmarking of control strategies for ATAD technology: a first approach to the automatic control of sludge treatment systems

  1. Zambrano, J.A. 2
  2. Gil-Martinez, M. 3
  3. Garcia-Sanz, M. 1
  4. Irizar, I. 2
  1. 1 Universidad Pública de Navarra
    info
    Universidad Pública de Navarra

    Pamplona, España

    ROR https://ror.org/02z0cah89

    Erakundearen kokapen geografikoa Universidad Pública de Navarra
  2. 2 Universidad de Navarra
    info
    Universidad de Navarra

    Pamplona, España

    ROR https://ror.org/02rxc7m23

    Erakundearen kokapen geografikoa Universidad de Navarra
  3. 3 Universidad de La Rioja
    info
    Universidad de La Rioja

    Logroño, España

    ROR https://ror.org/0553yr311

    Erakundearen kokapen geografikoa Universidad de La Rioja
Aldizkaria:
Water Science and Technology

ISSN: 0273-1223

Argitalpen urtea: 2009

Alea: 60

Zenbakia: 2

Orrialdeak: 409-417

Mota: Artikulua

DOI: 10.2166/WST.2009.338 PMID: 19633383 SCOPUS: 2-s2.0-69749083480 WoS: WOS:000268681600016 GOOGLE SCHOLAR

Beste argitalpen batzuk: Water Science and Technology

Garapen Iraunkorreko Helburuak

info

Aurora SDG adimen artifizialaren eredua erabiliz lortutako ODS sailkapena.

Laburpena

Autothermal Thermophilic Aerobic Digestion (ATAD technology) is a promising alternative to conventional digestion systems. Aeration is a key factor in the performance of these kinds of reactors, in relation to effluent quality and operating costs. At present, the realisation of automatic control in ATADs is in its infancy. Additionally, the lack of robust sensors also makes the control of these processes difficult: only redox potential and temperature sensors are reliable for operation in full-scale plants. Based as it is on the existing simulation protocols for benchmarking of control strategies for wastewater treatment plants (WWTP), this paper presents the definition and implementation of a similar protocol but specifically adapted to the needs of ATAD technology. The implemented simulation protocol has been used to validate two different control strategies for aeration (ST1 and ST2). In comparison to an open-loop operation for the ATAD, simulation results showed that the ST1 strategy was able to save aeration costs of around 2-4%. Unlike ST1, ST2 achieved maximum sludge stabilisation but at the expense of higher aeration costs. © IWA Publishing 2009.